Industrial Power Supply 350W
- 5 x 3 x 1 Inch Form factor
- 350 Watts with Forced Air Cooling & 200 Watts with Convection Cooling
- High efficiency up to 94%
- -40 to 70 °C degree operating temperature*
- 12V / 0.5A Fan Output, Thermal Shut-down protection
- 2.56m Hours, Telcordia -SR332-issue 3 MTBF
- Standby Power < 0.5W
- Approved to EN60950-1 2nd Edition
Detailed description
| Electrical performance | |
|---|---|
| Input Voltage | 90-264 VAC/390 VDC, Universal (Derate from 100% at 100V AC to 90% at 90V AC) |
| Input Frequency | 47-63 Hz |
| Input Current | 115 VAC: 3.6 A max. 230 VAC: 1.8 A max. |
| Standby Power | less than 0.5W typical |
| Inrush Current | 115 VAC – 25 A, 230 VAC – 45 A, 264 VAC – 75 A |
| Leakage Current | 300 uA Typical |
| Efficiency | 94%(48V,58V), 93%(24V,30V), 92%(12V,15V) |
| Hold-up Time | Full Load > 8 ms typical Convection Load > 14 ms typical |
| Power Factor | exceeds 0.95 with Full Load |
| Output Power | up to 350W with 375 LFM, upto 200W Convection |
| Output Voltage Adjustability | +/-3% |
| Line Regulation | +/-0.5% |
| Load Regulation | +/-1% |
| Transient Response | 50-100% step load change, at 0.1A/uS slew rate, 50% duty cycle, 50Hz=5%, recovery time <5 ms |
| Rise Time | 55 ms typical |
| Set Point Tolerance | +/-1% |
| Over Current Protection | >110% ,Hiccup mode / Auto Recovery |
| Over Voltage Protection | 110 to 140%, Hiccup mode / Auto Recovery |
| Short Circuit Protection | Hiccup mode / Auto Recovery |
| Switching Frequency | PFC – 70 to 130 KHz, PWM – 50-80 KHz |
| Operating Temperature | -40 to + 70°C, -40 to 0°C startup is guaranteed with spec deviation (ref note 6) |
| Storage Temperature | -40 to + 85°C |
| Relative Humidity | 5% to 95%, noncondensing |
| Altitude | Operating: 16,000 ft.; Nonoperating: 40,000 ft. |
| MTBF | 2.56m Hours, Telcordia -SR332-issue 3 |
| Isolation Voltage | Input to Output – 3000V AC for ITE application Input to GND - 1500 VAC |
| Cooling | 350W with 375 LFM forced air cooling at 100 to 264VAC 200W with natural convection cooling at 100 to 264VAC |


NOTES
- Ripple is peak to peak with 20 MHz bandwidth and 10 µF (Tantalum capacitor) in parallel with a 0.1 µF capacitor at rated line voltage and load ranges.
- Combined output power of main output, fan supply shall not exceed the max. Power rating.
- Fan supply output voltage tolerance including set point accuracy, line, and load regulation is +/-10% and Ripple and noise are less than 10%.
- Specifications are for nominal input voltage, 25°C unless otherwise stated.
- Thermal shutdown feature: The power supply goes in hiccup mode when the temperature of PCB exceeds 110 °C (+/-10 °C).
- Output ripple can be more than 10% of the output voltage.




Datasheet
Industrial 350W